Troubleshooting of SHxxRS ground fault (Error Code 106)

Applicable to: SHxxRS series

Updated over a week ago

In addition to the Error Code 106 mentioned in the troubleshooting, it should be noted that the ground wires in the PV & storage system (including batteries) should be connected to the same PE-Bar respectively. If the requirements are not met, the Error Code 106 will be reported.

In the case of SHxxRS inverter, the Backup port PE should be connected to the PE Bar even if the backup function is not used.