Can Sungrow 1-phase Microinverters be connected to my 3-phase system?

Applicable to: SxxxS series

Updated over a week ago

Yes, it is possible.

To be able to make this design, the same power microinverters shall be connected to each phase, as shown in the illustration.

For this,

three S450S

up to 3 panels -->

1350 Wac

three S800S

up to 6 panels -->

2400 Wac

three S1600S

up to 12 panels -->

3200 Wac

can be used.


For further information, please download the user manual accordingly: