Fault codes and troubleshooting steps 024_025

Applicable to: SGxxCX-series

Updated over a week ago

Fault Name

Bus voltage imbalance protection (fault code: 024/025)

Fault Type

Failure shutdown

Fault Condition

When the bus voltage is greater than 900 V and the negative half bus voltage deviation exceeds 100 V (the average midpoint offset exceeds 100 V) for longer than the set time or 150V instantly.

Troubleshooting steps and methods

1. If this fault occurs in batches in the whole array, first check whether there is single-phase grounding and short circuit between phases on the AC side.

2. Contact SUNGROW Service for inverter replacement.