In the event of Fault Code 017 being informed through the App, the following corrective measures shall be taken:
Grid Voltage Unbalance (fault code: 017)
Fault name | Grid Voltage Unbalance (fault code: 017) |
Fault type | Failure shutdown |
Fault condition | The inverter detects unbalanced three-phase grid voltage |
Steps and method of troubleshooting | Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly: |
keywords: imbalance, unbalance
For further information, please download the user manual here.
This manual is intended for professional technicians who are responsible for installation, operation, maintenance and troubleshooting of inverters, and users who need to check inverter parameters. The inverter must only be installed by professional technicians.
The professional technician is required to meet the following requirements:
Know electronic, electrical wiring and mechanical expertise, and be familiar with electrical and mechanical schematics.
Have received professional training related to the installation, commissioning and troubleshooting of electrical equipment.
Be able to quickly respond to hazards or emergencies that occur during installation, commissioning and troubleshooting.
Be familiar with local standards and relevant safety regulations of electrical systems.
Read this manual thoroughly and understand the safety instructions related to operations.